PROBLEM POSSIBLE CAUSE SOLUTION
• Air pressure switch has not
made contact.
• High gas pressure switch has
activated.
• Low gas pressure switch has
activated.
Have a qualified electrician
troubleshoot and correct the
problem.
Cannot initiate a start
sequence.
Check air pressure switch
adjustment.
Check air filter.
Check blower rotation.
Check outlet pressure from
blower.
Be sure the main power to the
system is switched to the “on”
position.
• Purge cycle not completed.
Check flame safeguard system
or purge timer.
• Malfunction of the flame
safeguard system (e.g., shorted-
out flame sensor or electrical
noise in the sensor line).
• No power to the control unit.
• Main power is off.
Start-up sequence runs but
burner does not light.
Open pilot gas cock.
Increase gas flow. See page 17.
• Gas pressure into pilot
regulator too low.
Check outgoing gas pressure of
main regulator; increase if
necessary.
• Pilot gas cock closed.
• Pilot solenoid valve does not
open.
Have qualified electrician check
power supply to solenoid.
• Gas adjusting valve set too low.
• Air in the pilot gas line.
Repeat start-up several times to
purge air from gas line.
PILOT IGNITION ONLY
PILOT IGNITION OR DIRECT SPARK
No ignition:
• Attempting to ignite at inputs
greater than 60% (direct spark).
• Weak or non-existent spark.
Reduce start point gas flow.
Verify control circuit.
Verify ignition transformer is a
6,000 - 8,000 volt transformer.
(Not half-wave)
• There is no power to the
ignition transformer.
Restore the power to the
ignition transformer.
• Open circuit between the
ignition transformer and the
igniter.
Repair or replace the wiring to
the igniter.
TROUBLESHOOTING PROCEDURES
Check incomming gas pressure;
adjust if necessary.
Check pressure switch setting
and operation.