Eclipse Winnox Burner, WX Series, V2, Installation Guide 111, 2/26/2010
Ŷ Do not attempt to remove the rear cover by
removing the inner circle bolts \. Internal burner
parts will be damaged.
e. Remove bolts ].
f. Remove the rear cover / nozzle assembly Z from the
burner housing [.
g. To reassemble, follow this sequence in the reverse
order.
NOTE:
The combustor can be inspected only by removing
the burner from the chamber wall or entering the chamber.
Figure 5.2 Nozzle Inspection
Recommended Spare Parts
To make sure that the downtime of the system is as short
as possible in case of a failure, you should keep a stock of
spare parts. Please refer to the Eclipse Product
Information Center (EPIC) for a full listing of spare parts:
http://www.eclipsenet.com/products
Troubleshooting
CAUTION
Problem Possible Cause Solution
Start-up sequence runs but
burner does not light.
No ignition. There is no power to the ignition
transformer.
Restore the power to the ignition
transformer.
No ignition. Open circuit between the
ignition transformer and the igniter.
Repair or replace the wiring to the igniter.
No ignition. The igniter needs cleaning. Clean the igniter.
No ignition. The igniter is not correctly
grounded to the burner.
Clean the threads on the igniter and the
burner. NOTE:
Do not apply grease to the
threads on the igniter.
No ignition. Igniter insulator is broken.
Igniter is grounding out.
Inspect the igniter. Replace if broken.
Igniter grounds out, igniter is bent. Inspect ignitor by removing nozzle and rear
cover. Check if gaps exist, readjust if
needed.
Not enough gas. The gas pressure into the
ratio regulator is too low.
Check the start-up setting. Measure the
gas pressures and adjust where necessary.
Not enough gas. The impulse line to the
ratio regulator is leaking.
Repair any leaks.
Not enough gas. The adjustable orifice
valve is not open far enough.
Adjust bypass or low fire gas.
Not enough gas. Start gas solenoid valve
does not open.
Check the solenoid valve coil for proper
operation. Replace it if necessary.
Not enough gas. Gas valve does not open. Check the wiring to the automatic gas shut-
off valve. Check the output from the flame
safeguard. Open manual gas cock.
Not enough gas. Ratio regulator is
incorrectly set.
Adjust the ratio regulator to the proper
setting.
No flame signal. Broken flamerod and/or
dirty UV scanner lens.
Inspect and clean sensor. Replace if
necessary.
Too much gas. Gas butterfly valve too far
open.
Check for proper setting.